Shower head and ceiling settings should comply with regulations

Update:30-08-2019
Summary:

Except for the ceiling type shower head and the shower […]

Except for the ceiling type shower head and the shower head provided under the ceiling, the distance between the vertical type and the drooping type standard coverage area shower head and the enlarged coverage area shower head splash plate and the top plate shall be 75mm~150mm, and shall meet the following requirements:

1. When the shower head is arranged on the plane below the bottom surface of the beam or other obstacles, the distance between the splash plate and the top plate should not exceed 300mm, and the vertical distance between the splash plate and the bottom surface of the obstacle such as the beam should be 25mm~100mm.

2. When shower heads are arranged between the beams, the distance between the shower heads and the beams shall be in accordance with the provisions of Article 7.2.1 of this code. When there is difficulty, the distance between the splash plate and the top plate should not exceed 550mm. shower heads arranged between the beams, when the distance between the splash plate and the top plate reaches 550 mm and still cannot meet the requirements of Article 7.2.1 of this code, a shower head should be added below the bottom of the beam.

3. The shower head below the ribbed beam, the vertical distance between the splashing plate and the bottom of the ribbed beam should be 25mm~100mm.